Optimal devices for every application
Electronic controllers, series THP, TDH, TDF are mostly used for control of temperature, pressure and humidity.
Programmable sensor inputs
The programmable sensor input allows for direct connection of temperature probes ( RTD, TC ) or normalized analog signals ( 0/1..5V, 0/2..10V, 0/4..20 mA ) for different signal sensors ( e.g. pressure sensors, humidity sensors... )
Control modes / alarm outputs
The controllers are available with PID, 2-point or 3-point control and 3-point motor valve control.
Up to 5 outputs as relais, SSR or norm signal are available.
Manifold alarm functions are programmable, e.g. it is possible to adjust the hysteresis, alarm output activity, start up behaviour and alarm LATCH.
|
 |
|
|
|
|
|
|
THP 94
Autotuned, digital controller for temperature and process values
PID; 2-point or 3-point control
3-point motor valve control
Measuring inputs: 1
- Resistance thermometer: Pt 100 / 3-wire
- Thermocouples: J, K, R, S, T, B, E, N, L, U
- Norm signals:
0(4) ... 20 mA,
0(1) ... 5 V,
0(2) ... 10 V
Outputs: max. 5, up to 2 x contr. output
resp. 4 x alarm outputs possible
- Relay: change over contact:
6A / 2,25 A / 250 VAC
- Solid state relay ( SSR drive ):
24 VDC / 25 mA
- Norm signals: (as control outputs)
0(4) ... 20 mA,
0(2) ... 10 V
|
 |
|
|
|
|
|
|
THP 98
Autotuned, digital controller for temperature values
PID; 2-point or 3-point control
Measuring inputs: 1
- Resistance thermometer: Pt 100 / 3-wire
- Thermocouples: J, K, R, S, T
Outputs: max. 5, up to 2 x contr. output
resp. 3 x alarm outputs possible
- Relay: change over contact:
6A / 2,25 A / 250 VAC
- Solid state relay ( SSR drive ):
24 VDC / 25 mA |
 |
|
|
|
|
|
|
THP 84
Autotuned, digital controller for temperature and process values
PID; 2-point or 3-point control
3-point motor valve control
Measuring inputs: 1
- Resistance thermometer: Pt 100 / 3-wire
- Thermocouples: J, K, R, S, T, B, E, N, L, U
- Norm signals:
0(4) ... 20 mA,
0(1) ... 5 V,
0(2) ... 10 V
Outputs: max. 2, up to 2 x contr. output
resp. alarm outputs possible
- Relay: close contact:
6A / 2,25 A / 250 VAC
- Solid state relay ( SSR drive ):
24 VDC / 25 mA
- Norm signals: ( as control outputs )
0(4) ... 20 mA,
0(2) ... 10 V |
 |
|
|
|
|
|
|
TLK 43 / TLK 42
Autotuned, digital controller for temperature and process values
PID; 2-point or 3-point control
3-point motor valve control (TLK 43 opt.)
Measuring inputs: 1
free programmable multi input
- Resistance thermometer: Pt 100 / 3-wire
- Semi conductor:
PTC: KTY 81 - 121 / 2-wire
NTC: 103 AT-2 / 2-wire
- Thermocouples: J, K, S
- Norm signals:
0(4) ... 20 mA,
0(1) ... 5V,
0(2) ... 10 V
Outputs: max. 4, up to 2 x contr. output
resp. 3 x alarm outputs possible
- Relay, close contact
4A / 2 A / 250 VAC
- Solid state relay ( SSR drive ):
14 VDC / 20 mA
- Norm signals: (as control outputs)
0(4) ... 20 mA,
0(2) ... 10 V (TLK 43 opt.) |
 |
|
|
|
|
|
|
TLK 41
Autotuned, digital controller for temperature and process values
PID; 2-point or 3-point control
Measuring inputs: 1
free programmable multi input
- Resistance thermometer: Pt 100 / 3-wire
- Semi conductor:
PTC: KTY 81 - 121 / 2-wire
NTC: 103 AT-2 / 2-wire
- Thermocouples: J, K, S
- Norm signals:
0(4) ... 20 mA,
0(1) ... 5V,
0(2) ... 10 V
Outputs: max. 4, up to 2 x contr. output
resp. 3 x alarm outputs possible
- Relay, close contact
4A / 2 A / 250 VAC
- Solid state relay ( SSR drive ):
14 VDC / 20 mA |
 |
|
|
|
|
|
|
THP 96
Autotuned, digital controller for temperature and process values
PID; 2-point or 3-point control
Measuring inputs: 1
- Resistance thermometer: Pt 100, Ni 100 / 3-wire
- Semi conductor PTC: KTY 81-121 / 2-wire
- Thermocouples: J, K, S
- Norm signals:
0 ... 20 mA,
4 ... 20 mA,
0 ... 10 V
Outputs: max. 2, up to 2 x contr. output
resp. alarm outputs possible
- Relay: change over contact:
8A / 3 A / 250 VAC
- Solid state relay ( SSR drive ):
12 VDC / 25 mA |
 |
|
|
|
|
|
|
THP 72
Autotuned, digital controller for temperature and process values
PID; 2-point or 3-point control
Measuring inputs: 1
- Resistance thermometer: Pt 100, Ni 100 / 3-wire
- Semi conductor PTC: KTY 81-121 / 2-wire
- Thermocouples: J, K, S
- Norm signals:
0 ... 20 mA,
4 ... 20 mA,
0 ... 10 V
Outputs: max. 2, up to 2 x contr. output
resp. alarm outputs possible
- Relay: change over contact,
8A / 3 A / 250 VAC
- Solid state relay ( SSR drive ):
12 VDC / 25 mA |
 |
|
|
|
|
|
|
THP 48
Autotuned, digital controller for temperature and process values
PID; 2-point or 3-point control
Measuring inputs: 1
- Resistance thermometer: Pt 100, Ni 100 / 3-wire
- Semi conductor PTC: KTY 81-121 / 2-wire
- Thermocouples: J, K, S
- Norm signals:
0 ... 20 mA,
4 ... 20 mA,
0 ... 10 V
Outputs: max. 2, up to 2 x contr. output
resp. alarm outputs possible
- Relay: change over contact:
8A / 3 A / 250 VAC
- Solid state relay ( SSR drive ):
12 VDC / 25 mA |
 |
|
|
|
|
|
|
THP 24
Autotuned, digital controller for temperature and process values
PID; 2-point or 3-point control
Measuring inputs: 1
- Resistance thermpmeter: Pt 100, Ni 100 / 3-wire
- Semi conductor PTC: KTY 81-121 / 2-wire
- Thermocouples: J, K, S
- Norm signals:
0 ... 20 mA,
4 ... 20 mA,
0 ... 10 V
Outputs: max. 2, up to 2 x contr. output
resp. alarm outputs possible
- Relay: close contact:
8A / 3 A / 250 VAC
- Solid state relay ( SSR drive ):
6 VDC / 25 mA |
 |
|
|
|
|
|
|
THP 35
Autotuned, digital controller for temperature and process values
PID; 2-point or 3-point control
Measuring inputs: 1
- Resistance thermometer: Pt 100, Ni 100 / 3-wire
- Semi conductor PTC: KTY 81-121 / 2-wire
- Thermocouples: J, K, S
- Norm signals:
0 ... 20 mA,
4 ... 20 mA,
0 ... 10 V
Outputs: max. 2, up to 2 x contr. output
resp. alarm outputs possible
- Relay: change over contact:
8A / 3 A / 250 VAC
- Solid state relay ( SSR drive ):
12 VDC / 25 mA |
 |
|
|
|
|
|
|
TDH 02
Autotuned, digital controller for temperature and process values
PID; 2-point or 3-point control
Measuring inputs: 1
- Resistance thermometer: Pt 100, Ni 100 / 3-wire
- Semi conductor PTC: KTY 81-121 / 2-wire
- Thermocouples: J, K, S
- Norm signals:
0 ... 20 mA,
4 ... 20 mA,
0 ... 10 V
Outputs: max. 2, up to 2 x contr. output
resp. alarm outputs possible
- Relay: change over contact:
8A / 3 A / 250 VAC
- Solid state relay ( SSR drive ):
12 VDC / 25 mA |
 |
|
|
|
|
| |
|
TCPDE
Analog contoller for temperature value
PID or 2-point control
Measuring inputs: 1
- Resistance thermometer: Pt 100 / 3-wire
- Thermocouples: J, K
Outputs: 1 x relay:
- change over contact: 8 A / 3 A / 250 VAC |
 |
|
|
|
|
|
|
TDF 11
Digital controller for temperature values
2-point control
Measuring inputs: 1
- Semi conductor PTC: KTY 81-121 / 2-wire
Outputs: 1 x relay: change over contact,
8A / 3 A / 250 VAC
Displays: 1 line, 2 1/2-digits, 7-seg. LED
- Process value: red, 20 mm high |
 |
|
|
|
|
| |
|
TDL 61
Digital controller for temperature values
2-point control
Measuring inputs: 1
- Semi conductor NTC: 103 AT-2 / 2-wire
Outputs: 1 x relay:
- change over contact: 8 A / 3 A / 250 VAC
- change over contact: 16 A / 6 A / 250 VAC (opt.) |
 |
|
|
|
|
| |
|
TDL 51
Digital controller for temperature values
2-point control
Measuring inputs: 1
- Semi conductor NTC: 103 AT-2 / 2-wire
Outputs: 1 x relay:
- change over contact: 8 A / 3 A / 250 VAC
- change over contact: 16 A / 6 A / 250 VAC (opt.) |
 |
|
|
|
|
|
|
Electronic measuring device with manual selector switch
Series TS 9000 TM
Series TS 9000 TM units are used wherever a large number of measuring channels ( sensors ) have to be scanned with a measuring unit.
The instruments can be used with resistance thermometers, standard thermocouples and standard signals.
The 3 1/2-digit display is 11 or 20 mm high. The measuring channels are selected via keys or rotary switches. |
 |
|
|
|
|
|
|
Electronic measuring device with / without monitoring function
Series TS 9000
The series TS 9000 with it's modular construction can be used for a wide variety of measuring and monitoring functions.
The instruments are equipped with an input circuit for either the direct connection of resistance thermometers, thermocouples or a voltage / current input.
The 3 1/2-digit display can be supplied 11 or 20 mm high, depending on the housing size |
 |
|
|
|
|
|
|
TS 31000
Temperature measuring instrument with contacless operable selector switch
- 16 or 32 inputs for thermocouples type K, E, J, T, S, B or R
- type of thermocouple selectable by the user at the spot
- high-contrast 4-digit LED display easy to read even from a greater distance
- 2-line alphanumeric LCD text display
- contactless operation: selection of the measuring point and programming via 2 light reflecting buttons
- pre-configurable at works for up to 16 different applications, e.g. engine types |
 |
|
|
|
|
|
|
SIKA measured data acquisition and monitoring systems
TS 6700 TA and TS 16700 TA series
Unbroken monitoring!
Series TS 6700 TA measured data monitoring systems monitor process variables in machines, systems and process technology and detect when they cross threshold values.
The multi-channel measurement module of the monitoring unit allows resistance thermometers and thermoelementes to be connected directly, or any sensor with a standard signal output. This means that the system can be used for monitoring virtually all physical variables. |
 |
|
|
|
|
|
|
Measured data acquisition and monitoring systems
TS 6700 TA
sensor inputs
- Resistance thermometer
- Thermoelementes
- Standard signals
Measuring point
- 2-position, 7-segemnt, red, 11 mm high
Measured value
- 3 1/2-position, 7-segment, red, 11 mm high
Alarms 1-3
- In each case 2-position, 7-segment, red, 11 mm high
- Multiple alarms are displayed by the corresponding
display flashing
Measurement ranges and resolution
- -199,9...+199,9 °C / 0,1 K or +200...+1790 °C
( automatic range selection )
Measurement rate
- 7 measurements per second |
 |
|
|
|
|
 |
|
Measured data acquisition and monitoring systems
TS 16700 TA
sensor inputs
- Thermoelements
Measuring point
- 2-position, 7-segemnt, red, 11 mm high
Measured value
- 3 1/2-position, 7-segment, red, 11 mm high
Alarms 1-3
- In each case 2-position, 7-segment, red, 11 mm high
- Multiple alarms are displayed by the corresponding
display flashing
Measurement ranges and resolution
- -199,9...+199,9 °C / 0,1 K or +200...+1790 °C
( automatic range selection )
Measurement rate
- 7 measurements per second |
 |
| |
|
|
|
|